CHAPTER 5 Ladder
diagram
Introduction
5.1 Ladder diagram
5.2 Normally open and normally closed contacts
5.3 Brief example
Introduction
Programmable controllers are generally programmed in ladder
diagram (or "relay diagram") which is nothing but a symbolic
representation of electric circuits. Symbols were selected that actually looked
similar to schematic symbols of electric devices, and this has made it much
easier for electricians to switch to programming PLC controllers. Electrician
who has never seen a PLC can understand a ladder diagram.
5.1 Ladder diagram
There are several languages designed for user communication
with a PLC, among which ladder diagram is the most popular. Ladder diagram
consists of one vertical line found on the left hand side, and lines which
branch off to the right. Line on the left is called a "bus bar", and
lines that branch off to the right are instruction lines. Conditions which lead
to instructions positioned at the right edge of a diagram are stored along
instruction lines. Logical combination of these conditions determines when and
in what way instruction on the right will execute. Basic elements of a relay
diagram can be seen in the following picture.
Most instructions require at least one operand, and often
more than one. Operand can be some memory location, one memory location bit, or
some numeric value -number. In the example above, operand is bit 0 of memory
location IR000. In a case when we wish to proclaim a constant as an operand,
designation # is used beneath the numeric writing (for a compiler to know it is
a constant and not an address.)
Based on the picture above, one should note that a ladder
diagram consists of two basic parts: left section also called conditional, and
a right section which has instructions. When a condition is fulfilled,
instruction is executed, and that's all!
Picture above represents a example of a ladder diagram where
relay is activated in PLC controller when signal appears at input line 00.
Vertical line pairs are called conditions. Each condition in a ladder diagram
has a value ON or OFF, depending on a bit status assigned to it. In this case,
this bit is also physically present as an input line (screw terminal) to a PLC
controller. If a key is attached to a corresponding screw terminal, you can
change bit status from a logic one status to a logic zero status, and vice
versa. Status of logic one is usually designated as "ON", and status
of logic zero as "OFF".
Right section of a ladder diagram is an instruction which is
executed if left condition is fulfilled. There are several types of
instructions that could easily be divided into simple and complex. Example of a
simple instruction is activation of some bit in memory location. In the example
above, this bit has physical connotation because it is connected with a relay
inside a PLC controller. When a CPU activates one of the leading four bits in a
word IR010, relay contacts move and connect lines attached to it. In this case,
these are the lines connected to a screw terminal marked as 00 and to one of
COM screw terminals.
5.2 Normally open and normally closed contacts
Since we frequently meet with concepts "normally
open" and "normally closed" in industrial environment, it's
important to know them. Both terms apply to words such as contacts, input,
output, etc. (all combinations have the same meaning whether we are talking
about input, output, contact or something else).
Principle is quite simple, normally open switch won't
conduct electricity until it is pressed down, and normally closed switch will
conduct electricity until it is pressed. Good examples for both situations are
the doorbell and a house alarm.
If a normally closed switch is selected, bell will work
continually until someone pushes the switch. By pushing a switch, contacts are
opened and the flow of electricity towards the bell is interrupted. Of course,
system so designed would not in any case suit the owner of the house. A better
choice would certainly be a normally open switch. This way bell wouldn't work
until someone pushed the switch button and thus informed of his or her presence
at the entrance.
Home alarm system is an example of an application of a
normally closed switch. Let's suppose that alarm system is intended for
surveillance of the front door to the house. One of the ways to
"wire" the house would be to install a normally open switch from each
door to the alarm itself (precisely as with a bell switch). Then, if the door
was opened, this would close the switch, and an alarm would be activated. This
system could work, but there would be some problems with this, too. Let's suppose
that switch is not working, that a wire is somehow disconnected, or a switch is
broken, etc. (there are many ways in which this system could become
dysfunctional). The real trouble is that a homeowner would not know that a
system was out of order. A burglar could open the door, a switch would not
work, and the alarm would not be activated. Obviously, this isn't a good way to
set up this system. System should be set up in such a way so the alarm is
activated by a burglar, but also by its own dysfunction, or if any of the
components stopped working. (A homeowner would certainly want to know if a
system was dysfunctional). Having these things in mind, it is far better to use
a switch with normally closed contacts which will detect an unauthorized
entrance (opened door interrupts the flow of electricity, and this signal is
used to activate a sound signal), or a failure on the system such as a
disconnected wire. These considerations are even more important in industrial
environment where a failure could cause injury at work. One such example where
outputs with normally closed contacts are used is a safety wall with trimming
machines. If the wall doors open, switch affects the output with normally
closed contacts and interrupts a supply circuit. This stops the machine and
prevents an injury.
Concepts normally open and normally closed can apply to
sensors as well. Sensors are used to sense the presence of physical objects,
measure some dimension or some amount. For instance, one type of sensors can be
used to detect presence of a box on an industry transfer belt. Other types can
be used to measure physical dimensions such as heat, etc. Still, most sensors
are of a switch type. Their output is in status ON or OFF depending on what the
sensor "feels". Let's take for instance a sensor made to feel metal
when a metal object passes by the sensor. For this purpose, a sensor with a
normally open or a normally closed contact at the output could be used. If it
were necessary to inform a PLC each time an object passed by the sensor, a
sensor with a normally open output should be selected. Sensor output would set
off only if a metal object were placed right before the sensor. A sensor would
turn off after the object has passed. PLC could then calculate how many times a
normally open contact was set off at the sensor output, and would thus know how
many metal objects passed by the sensor.
Concepts normally open and normally closed contact ought to
be clarified and explained in detail in the example of a PLC controller input and
output. The easiest way to explain them is in the example of a relay.
Normally open contacts would represent relay contacts that
would perform a connection upon receipt of a signal. Unlike open contacts, with
normally closed contacts signal will interrupt a contact, or turn a relay off.
Previous picture shows what this looks like in practice. First two relays are
defined as normally open , and the other two as normally closed. All relays
react to a signal! First relay (00) has a signal and closes its contacts.
Second relay (01) does not have a signal and remains opened. Third relay (02)
has a signal and opens its contacts considering it is defined as a closed
contact. Fourth relay (03) does not have a signal and remains closed because it
is so defined.
Concepts "normally open" and "normally
closed" can also refer to inputs of a PLC controller. Let's use a key as
an example of an input to a PLC controller. Input where a key is connected can
be defined as an input with open or closed contacts. If it is defined as an
input with normally open contact, pushing a key will set off an instruction
found after the condition. In this case it will be an activation of a relay 00.
If input is defined as an input with normally closed
contact, pushing the key will interrupt instruction found after the condition.
In this case, this will cause deactivation of relay 00 (relay is active until
the key is pressed). You can see in picture below how keys are connected, and
view the relay diagrams in both cases.
Normally open/closed conditions differ in a ladder diagram
by a diagonal line across a symbol. What determines an execution condition for
instruction is a bit status marked beneath each condition on instruction line.
Normally open condition is ON if its operand bit has ON status, or its status
is OFF if that is the status of its operand bit. Normally closed condition is
ON when its operand bit is OFF, or it has OFF status when the status of its
operand bit is ON.
When programming with a ladder diagram, logical combination
of ON and OFF conditions set before the instruction determines the eventual
condition under which the instruction will be, or will not be executed. This
condition, which can have only ON or OFF values is called instruction execution
condition. Operand assigned to any instruction in a relay diagram can be any
bit from IR, SR, HR, AR, LR or TC sector. This means that conditions in a relay
diagram can be determined by a status of I/O bits, or of flags, operational
bits, timers/counters, etc.
5.3 Brief example
Example below represents a basic program. Example consists
of one input device and one output device linked to the PLC controller output.
Key is an input device, and a bell is an output supplied through a relay 00
contact at the PLC controller output. Input 000.00 represents a condition in
executing an instruction over 010.00 bit. Pushing the key sets off a 000.00 bit
and satisfies a condition for activation of a 010.00 bit which in turn
activates the bell. For correct program function another line of program is
needed with END instruction, and this ends the program.
The following picture depicts the connection scheme for this
example.
No comments:
Post a Comment